INMEL 25
INMEL 25 Calibrator is precise source of DC voltage with setting range
from 0 ÷ 2.5 V and resolution 1 µV.
The value of voltage generation is chosen by numerical keyboard and switch on LCD display or chosen by interface RS 232.
The display ground-lighting, which can be switched off, is especially useful in conditions of an insufficient lighting. The calibrator is equipped in output terminals, which enable four-wire load capacity connection.
The devices is destined for checking and regulation systems, industrial automatic devices such as regulators, recorders, meters etc. INMEL 25 can be also use for maintenance and service industrial automatic devices and electronic equipments.
from 0 ÷ 2.5 V and resolution 1 µV.
The value of voltage generation is chosen by numerical keyboard and switch on LCD display or chosen by interface RS 232.
The display ground-lighting, which can be switched off, is especially useful in conditions of an insufficient lighting. The calibrator is equipped in output terminals, which enable four-wire load capacity connection.
The devices is destined for checking and regulation systems, industrial automatic devices such as regulators, recorders, meters etc. INMEL 25 can be also use for maintenance and service industrial automatic devices and electronic equipments.
APPLICATION:
- standard of DC voltage,
- thermocouple simulation,
- calibration of regulators, recorders, measuring transducers,
- check and regulation of industry automatic devices.
Basic parameters
RANGE | SETTING RANGES | RESOLUTION |
2.5V | 0 .... +2499000μV | 1μV |
RANGE | ACCURACY | LOAD |
2.5V | 30ppm ±5 μV | 25 mA |
TIME STABILITY | 6 ppm/1000h |
Power supply | 230V ±10%, 50Hz |
Power consumption | 4VA max. |
Dimension | 250 x 80 x 330 mm |
Weight | 3.5 kg |